Zgryźliwość kojarzy mi się z radością, która źle skończyła.

Power factor correction
and harmonic filtering
Capacitors and banks 50 Hz
400 V network voltage
Rectimat 2
<< Back
The Rectimat 2 capacitor banks are
automatic compensation equipment in the
form of an enclosure or a cubicle according
to the power ratings.
Standard type
No polluted network (Gh/Sn
6
15 %)
Rectimat 2
400 V
(kvar)
Step
Type
(1)
Ref.
400 V
(kvar)
Step
Type
(1)
Ref.
7.5
3x2.5
Enclosure 1 NS100
52812
67.5
9x7.5
Enclosure 2 NS160
52830
10
4x2.5
Enclosure 1 NS100
52813
75
5x15
Enclosure 2 NS160
52612
12.5
5x2.5
Enclosure 1 NS100
52814
90
3x30
Cubicle 1
NS250
52613
15
3x5
Enclosure 1 NS100
52815
105
7x15
Cubicle 1
NS250
52614
17.5
7x2.5
Enclosure 1 NS100
52816
120
8x15
Cubicle 2
NS250
52615
20
4x5
Enclosure 1 NS100
52817
150
5x30
Cubicle 1
NS400
52616
52675
52617
22.5
3x7.5
Enclosure 1 NS100
180
6x30
Cubicle 1
NS400
25
5x5
Enclosure 1 NS100
52818
210
7x30
Cubicle 2
NS630
52618
52609
52619
30
4x7.5
Enclosure 1 NS100
240
8x30
Cubicle 2
NS630
3x10
Enclosure 1 NS100
52819
270
9x30
Cubicle 2
NS630
52620
Rectimat 2 enclosure 1
6x5
Enclosure 1 NS100
52820
315
7x45
Cubicle 3
NS630
52621
35
7x5
Enclosure 2 NS100
52821
360
8x45
Cubicle 3
C801
52622
37.5
5x7.5
Enclosure 1 NS100
52676
405
9x45
Cubicle 3
C801
52623
40
4x10
Enclosure 2 NS100
52822
450
5x90
Cubicle 3
C1001
52624
8x5
Enclosure 2 NS100
52823
495
11x45
Cubicle 4
C1001
52625
52610
52626
45
3x15
Enclosure 1 NS100
540
6x90
Cubicle 4
C1251
6x7.5
Enclosure 2 NS100
52677
585
13x45
Cubicle 4
C1251
52627
52824
52628
9x5
Enclosure 2 NS100
630
7x90
Cubicle 4
C1251
50
5x10
Enclosure 2 NS100
52825
675
15x45
Cubicle 4
CM1600
52629
52.5
7x7.5
Enclosure 2 NS160
52678
720
8x90
Cubicle 4
CM1600
52630
55
11x5
Enclosure 2 NS160
52826
765
17x45
Cubicle 4
CM1600
52631
60
4x15
Enclosure 2 NS160
52611
810
9x90
Cubicle 4
CM1600
52632
6x10
Enclosure 2 NS160
52827
855
19x45
Cubicle 4
CM2000
52633
8x7.5
Enclosure 2 NS160
52828
900
10x90
Cubicle 4
CM2000
52634
62.5 5x12.5 Enclosure 2 NS160
52829
(1)
recommended circuit breaker (out of supply)
Technical data
# capacitor rated voltage: 400 V, three-phase 50 Hz
# capacitance value tolerance: 0, +10 %
# insulation level:
5 0.69 kV
5 withstand 50 Hz 1 min: 2.5 kV.
# maximum permissible current: 1.3 In (400 V)
# maximum permissible voltage (8 hours over 24 hours as in IEC 60831): 450 V
# temperature class (400 V):
5 maximum temperature: 40 °C
5 average temperature over 24 hrs: 35 °C
5 average annual temperature: 25 °C
5 minimum temperature: -5 °C.
# degree of protection: IP31
# transformer 400/230 V to feed auxiliary supplies
# protection against direct contact (opened door)
# colour:
5 metal sheet: RAL 9002
5 bottom blanking plate: RAL 7021.
# standards: IEC 60439-1, EN 60439-1.
Rectimat 2 cubicle 1
Accessories for Rectimat 2
Ref.
Free-standing plinth for enclosures 1 and 2
52671
Plinth H = 250 for cubicle 1
52672
Rectimat 2 cubicle 3
Plinth H = 250 for cubicles 2 and 3
52673
Plinth H = 250 for cubicle 4
2 x
52673
437E3220.fm/18
Schneider Electric
 Power factor correction
and harmonic filtering
Capacitors and banks 50 Hz
400 V network voltage
Rectimat 2
Installation
# fixing:
5 enclosure: wall mounting or free standing with plinth (accessory)
5 cubicle: free standing cubicle or free standing with plinth (accessory).
# bottom connection of power cables to the busbar pads
# the CT (5 VA sec. 5 A), not supplied, is to be placed upstream from the
capacitorbank and loads
# it is not necessary to provide a 230 V/50 Hz power supply to supply the contactor
coils.
Options
# incoming circuit-breaker
# fixed base compensation
# extension
# load shedding (main-standby)
# top connection
# please consult us for other options.
Dimensions
Standard type
400 V
(kvar)
H
Type
Dimensions (mm)
Weight
(kg)
H
L
D
7.5
Enclosure 1
400
500
250
20
10
Enclosure 1
400
500
250
20
L
D
12.5
Enclosure 1
400
500
250
20
Rectimat 2 enclosures 1 and 2
15
Enclosure 1
400
500
250
20
17.5
Enclosure 1
400
500
250
20
20
Enclosure 1
400
500
250
20
22.5
Enclosure 1
400
500
250
20
25
Enclosure 1
400
500
250
20
30
Enclosure 1
400
500
250
20
H
35
Enclosure 2
800
500
250
25
37.5
Enclosure 1
400
500
250
20
40
Enclosure 2
800
500
250
25
45
3 x 15
Enclosure 1
400
500
250
25
6 x 7.5 - 9 x 5
Enclosure 2
800
500
250
25
L
D
50
Enclosure 2
800
500
250
25
Rectimat 2 cubicles 1 and 2
52.5
Enclosure 2
800
500
250
25
55
Enclosure 2
800
500
250
25
60
Enclosure 2
800
500
250
40
62.5
Enclosure 2
800
500
250
40
67.5
Enclosure 2
800
500
250
40
75
Enclosure 2
800
500
250
45
90
Cubicle 1
1050
550
500
60
105
Cubicle 1
1050
550
500
70
120
Cubicle 2
1050
800
500
70
H
150
Cubicle 1
1050
550
500
70
180
Cubicle 1
1050
550
500
75
210
Cubicle 2
1050
800
500
90
240
Cubicle 2
1050
800
500
100
270
Cubicle 2
1050
800
500
105
315
Cubicle 3
2100
800
500
155
360
Cubicle 3
2100
800
500
165
405
Cubicle 3
2100
800
500
170
L
D
450
Cubicle 3
2100
800
500
180
Rectimat 2 cubicles 3 and 4
495
Cubicle 4
2100
1600
500
300
540
Cubicle 4
2100
1600
500
305
585
Cubicle 4
2100
1600
500
315
630
Cubicle 4
2100
1600
500
325
675
Cubicle 4
2100
1600
500
330
720
Cubicle 4
2100
1600
500
340
765
Cubicle 4
2100
1600
500
345
810
Cubicle 4
2100
1600
500
355
855
Cubicle 4
2100
1600
500
360
900
Cubicle 4
2100
1600
500
370
Schneider Electric
437E3220.fm/19
 Power factor correction
and harmonic filtering
Capacitors and banks 50 Hz
400 V network voltage
Rectimat 2
The Rectimat 2 capacitor banks are
automatic compensation equipment in the
form of an enclosure or a cubicle according
to the power ratings.
Overrated type
Polluted network (15 % < Gh/Sn
6
25 %)
Rectimat 2
400 V
(kvar)
470 V
(kvar)
Step
Type
Recommended
circuit breaker (1)
Ref.
30
41
4 x 7,5
Enclosure 2
NS100
52635
45
62
6 x 7,5
Enclosure 2
NS100
52636
50
69
5 x 10
Enclosure 2
NS160
52637
80
110
8 x 10
Cubicle 2
NS250
52638
100
138
5 x 20
Cubicle 1
NS250
52639
120
166
6 x 20
Cubicle 1
NS400
52640
52641
160
221
8 x 20
Cubicle 2
NS400
180
249
9 x 20
Cubicle 2
NS400
52642
52643
210
290
6 x 35
Cubicle 2
NS630
245
338
7 x 35
Cubicle 3
NS630
52644
280
387
8 x 35
Cubicle 3
NS630
52645
315
435
9 x 35
Cubicle 3
C801
52646
350
483
10 x 35
Cubicle 3
C801
52647
Rectimat 2 enclosure 2
420
580
6 x 70
Cubicle 4
C1001
52648
455
628
13 x 35
Cubicle 4
C1001
52649
52650
525
725
15 x 35
Cubicle 4
C1251
560
773
8 x 70
Cubicle 4
C1251
52651
52652
630
870
9 x 70
Cubicle 4
CM1600
700
966
10 x 70
Cubicle 4
CM1600
52653
(1)
out of supply
Technical data
# capacitor rated voltage: 400 V, three-phase 50 Hz
# capacitance value tolerance: 0, +10 %
# insulation level:
5 0.69 kV
5 withstand 50 Hz 1 min: 2.5 kV.
# maximum permissible current: 1,5 In (400 V).
# maximum permissible voltage (8 hours over 24 hours as in IEC 60831): 517 V
# temperature class (400 V):
5 maximum temperature: 40 °C
5 average temperature over 24 hrs: 35 °C
5 average annual temperature: 25 °C
5 minimum temperature: -5 °C.
# degree of protection: IP31
# transformer 400/230 V to feed auxiliary supplies
# protection against direct contact (opened door)
# colour:
5 metal sheet: RAL 9002
5 bottom blanking plate: RAL 7021.
# standards: IEC 60439-1, EN 60439-1.
Rectimat 2 cubicle 1
Accessories for Rectimat 2
Ref.
Free-standing plinth for enclosures 1 and 2
52671
Plinth H = 250 for cubicle 1
52672
Plinth H = 250 for cubicles 2 and 3
52673
Plinth H = 250 for cubicle 4
2 x
52673
Rectimat 2 cubicle 3
437E3220.fm/20
Schneider Electric
 Power factor correction
and harmonic filtering
Capacitors and banks 50 Hz
400 V network voltage
Rectimat 2
Installation
# fixing:
5 enclosure: wall mounting or free standing with plinth (accessory)
5 cubicle: free standing cubicle or free standing with plinth (accessory).
# bottom connection of power cables to the busbar pads
# the CT (5 VA sec. 5 A), not supplied, is to be placed upstream from the capacitor
bank and loads
# it is not necessary to provide a 230 V/50 Hz power supply to supply the contactor
coils.
Options
# incoming circuit-breaker
# fixed base compensation
# extension
# load shedding (main-standby)
# top connection
# please consult us for other options.
Dimensions
Overrated type
400 V
H
470 V
Type
Dimensions (mm)
Weight
(kvar)
(kvar)
H
L
D
(kg)
30
41
Enclosure 2
800
500
250
40
45
62
Enclosure 2
800
500
250
45
L
D
50
69
Enclosure 2
800
500
250
45
Rectimat 2 enclosure 2
80
110
Cubicle 2
1050
800
500
70
100
138
Cubicle 1
1050
550
500
70
120
166
Cubicle 1
1050
550
500
75
160
221
Cubicle 2
1050
800
500
100
180
249
Cubicle 2
1050
800
500
105
210
290
Cubicle 2
1050
800
500
100
H
245
338
Cubicle 3
2100
800
500
160
280
387
Cubicle 3
2100
800
500
170
315
435
Cubicle 3
2100
800
500
180
350
483
Cubicle 3
2100
800
500
190
420
580
Cubicle 4
2100
1600
500
330
L
D
455
628
Cubicle 4
2100
1600
500
330
Rectimat 2 cubicles 1 and 2
525
725
Cubicle 4
2100
1600
500
345
560
773
Cubicle 4
2100
1600
500
370
630
870
Cubicle 4
2100
1600
500
390
700
966
Cubicle 4
2100
1600
500
390
H
L
D
Rectimat 2 cubicles 3 and 4
Schneider Electric
437E3220.fm/21
 Power factor correction
and harmonic filtering
Capacitors and banks 50 Hz
400 V network voltage
Rectimat 2
The Rectimat 2 capacitor banks are
automatic compensation equipment in the
form of an enclosure.
Detuned type
Highly polluted network (25 % < Gh/Sn
6
50 %)
Rectimat 2
400 V
(kvar)
Step
Type
Recommended
circuit breaker (1)
Ref.
25
2 x 12.5
Cubicle 2
NS100
52654
37.5
3 x 12.5
Cubicle 2
NS100
52655
50
4 x 12.5
Cubicle 2
NS100
52656
62.5
5 x 12.5
Cubicle 2
NS160
52657
75
3 x 25
Cubicle 2
NS160
52658
100
4 x 25
Cubicle 2
NS250
52659
52660
125
5 x 25
Cubicle 3
NS250
150
6 x 25
Cubicle 3
NS400
52661
52662
150
3 x 50
Cubicle 3
NS400
175
7 x 25
Cubicle 3
NS400
52663
200
4 x 50
Cubicle 3
NS400
52664
250
5 x 50
Cubicle 3B
NS630
52665
300
6 x 50
Cubicle 3B
NS630
52666
Rectimat 2 cubicle 2
350
7 x 50
Cubicle 4
C801
52667
400
8 x 50
Cubicle 4
C801
52668
52669
450
9 x 50
Cubicle 4
C1001
500
10 x 50
Cubicle 4
C1001
52670
52810
550
11 x 50
Cubicle 4B
C1251
600
12 x 50
Cubicle 4B
C1251
52811
(1)
out of supply
Technical data
# capacitor rated voltage: 400 V, three-phase 50 Hz
# tuning order: 4.3 (215 Hz)
# capacitance value tolerance: 0, +10 %
# insulation level:
5 0.69 kV
5 withstand 50 Hz 1 min: 2.5 kV
# maximum permissible current: 1.27 In (400 V)
# temperature class (400 V):
5 maximum temperature: 40 °C
5 average temperature over 24 hrs: 35 °C
5 average annual temperature: 25 °C
5 minimum temperature: -5 °C.
# degree of protection: IP31
# transformer 400/230 V to feed auxiliary supplies
# protection against direct contact (opened door)
# colour:
5 metal sheet: RAL 9002
5 bottom blanking plate: RAL 7021.
# standards: IEC 60439-1, EN 60439-1.
Rectimat 2 cubicle 3
Accessories for Rectimat 2
Ref.
Plinth H = 250 for cubicles detuned type 2 and 3
52673
Plinth H = 250 for cubicle detuned type 4
2 x
52673
Plinth H = 250 for cubicle detuned type 3B
52672 +
52673
Plinth H = 250 for cubicle detuned type 4B
2 x
52673 +
52672
437E3220.fm/22
Schneider Electric
 
  • zanotowane.pl
  • doc.pisz.pl
  • pdf.pisz.pl
  • hannaeva.xlx.pl